Viledon High Efficiency Pocket
Filters
| |
MF90 |
MF95 |
T90 |
T98 |
|
Rated Air Flow (cfm) |
2000 |
2000 |
2000 |
2000 |
|
Average Dust Spot Efficiency (%)* |
97 |
98 |
94 |
98 |
Initial Efficiency on Particles >1 micron
(%) |
98 |
>99 |
>95 |
>99 |
Initial Resistance
(in. w.g.) |
0.42 |
0.54 |
0.39 |
0.30 |
Burst Strength
(in. w.g.) |
>12 |
>12 |
>12 |
>12 |
|
Max. Temperature (ºF) |
160,
peaks 200 |
160,
peaks 200 |
160,
peaks 200 |
160,
peaks 200 |
|
UL 900 Classification |
Class 2 |
Class 2 |
Class 2 |
Class 2 |
|
Depth (in) |
26 |
26 |
26 |
26 |
|
Size Availability |
1/1, 5/6, 1/2, 1/4 and
S 1/1 - 18" |
1/1, 5/6, 1/2,
1/4 |
1/1, 1/2
|
1/1, 5/6, 1/2,
1/4 |
* According to ASHRAE 52.1 - 1992
 |
|
 |
|
Leak-free welded filter pockets |
|
Filter pockets foam-sealed into the frame |
 |
|
 |
| Intake air
filtration in a gas turbine (Clean air side) |
|
3-layered
progressive media structure |
 |
|
 |
|
Welded spacers for optimised aerodynamics
and low pressure drop |

|