Viledon High Efficiency Filters for Gas Turbine - 
12" MV Series and Depth-loading Filter Cartridges TFP 60 & TFP 90

     
 
MV75 MV85 MV95
Rated Air Flow (cfm) 2000 2000 2000
Average Dust Spot Efficiency (%)* 75 85 95
Initial Efficiency on Particles >1 micron
 (%)
>80 >91 >94
Initial Resistance
(in. w.g.)
0.27 0.29 0.33
Max. Temperature 
(ºF)
160,
peaks 175
160,
peaks 175
160,
peaks 175
UL 900 Classification Class 2  Class 2 Class 2
Depth (in) 11.5 11.5 11.5
Size Availability 1/1, 5/6, 5/5,1/2 1/1, 5/6, 5/5,1/2 1/1, 5/6, 5/5,1/2

Depth-loading filter cartridges TFP 60 and TFP 90
Unit TFP60 TFP90
Filtering area ft2 (m2) 33 (3)  120 (11)
Thermal stability °F (ºC) 158°F (70°C)
Peaks to 176°F (80°C)
158°F (70°C)
Peaks to 176°F (80°C)
Moisture resistance % 100 100
Average arrestance % 99 100
Average efficiency % 65 96
Nominal volume flow rate ft3/m (m3/h)) 600 (1000) 600 (1000)
Initial pressure drop in. H2O (Pa) 0.44 (108) 0.44 (109)
Recommended final pressure drop in. H2O (Pa) 3.2 (800) 3.2 (800)
Dust holding capacity*
(ISO Fine / 3.2 in. H2O, 800 Pa)
oz (g) 81 (2300) 42 (1200)

* According to ASHRAE 52.1 - 1992

Prog-Aufbau deut.tif (254122 Byte)   TFPAnw1.tif (212948 Byte)

Intake air filtration for a gas turbine with

 

 

 

AFP Filtros, C.A,

 

CARACAS / VENEZUELA

 

email  afpfiltros@gmail.com / afpfiltros@cantv.net